Erico 4.6m FRP Cantilevered Mast Terminal Elevation: 3.6 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Accessoires pour les appareils électriques Erico 4.6m FRP Cantilevered Mast Terminal Elevation: 3.6. ERICO 4.6m FRP Cantilevered Mast Terminal Elevation: 3.6m Above Structure User Manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 1
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
3.3 FT [1M]
2
-
-
1
-
3
-
1
-
3
-
2
®
Detail "A"
®
Not to Scale
Not to Scale
Typical ALOF1GS Wall Bracket Base
End View
Suggested three radial grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench
approximately 0.8m deep. The conductor is laid in the trench and is connected to ground rods. The
conductor in each trench is encased in GEM material. Ground rods must extend 3m below ground
level.
Note: This is one of several alternative installation methods.
Refer to ERICO installation manual for more details.
Typical Upper Termination
ERICORE Downconductor
Saddle
(ERICO Part # CONSAD/E2)
Saddle Mounting Screws
(ERICO Part # CONSADFX)
ERICORE Downconductor
Typical ERICORE Mount
Not to Scale
For complete
grounding system
refer to Detail "A"
Ground Inspection Well
Minimum 5/8" x 8' [16mm x 2.4M] long
ground rod in four locations
ERICORE Downconductor
ERICO CADWELD
Connection or
mechanical connection
Lightning Event Counter
(ERICO Part # LECIV)
Crow's Foot
(ERICO Part # GF302)
2/0 Conductor
(3 x 20 FT [6.1M] length)
Enclosed in GEM material
4.6m FRP Support Mast
(ERICO Part # FRP4.6MBLACK)
ERICORE Downconductor
with factory-fitted
upper termination
ERICO DYNASPHERE
(ERICO Part # D/SMKIV-SS)
Mast Support Bracket
(ERICO Part # ALOF1GS)
Lightning Event Counter
Refer to installation manual
for alternate locations
(ERICO Part # LECIV)
119.9mm
89.9mm
39.9mm
2 Holes,
10.9mm
3.3 FT [1M]
TECHNICAL SUPPORT
www.erico.com
IP79156_A
1 OF 1
INSTRUCTION SHEET
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
and from your ERICO customer service representative.
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be
completely
followed to ensure proper and safe installation and performance.
3.
Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and death.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
ERICO DYNASPHERE MKIV
Installation Instructions for 4.6m FRP Cantilevered Mast
Terminal Elevation: 3.6m Above Structure
© 2014
ERICO International Corporation.
Vue de la page 0
1

Résumé du contenu

Page 1 - ERICO DYNASPHERE MKIV

3.3 FT [1M] 2--1-3-1-3-2®Detail "A"®Not to ScaleNot to ScaleTypical ALOF1GS Wall Bracket BaseEnd ViewSuggested three radial grounding sys

Commentaires sur ces manuels

Pas de commentaire