INSTRUCTION SHEET
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH and LENTON are registered trademarks of ERICO International Corporation
TECHNICAL SUPPORT:
www.erico.com IP8284_A 1 of 2
2014 ERICO International Corporation
ERICO® INTERCEPTOR Terminal Testing
SI25i, SI40i, and SI60i Series
The procedure below is to provide guidance for testing of the ERICO INTERCEPTOR SI25i, SI40i and SI60i air
terminals using commonly available test equipment.
Tester unit can either be: “U1731C” or equivalent. Clips must be large enough to grip the 28 mm terminal.
Procedure to test ERICO INTERCEPTOR Air Terminals SIXXi range:
A) Connect 2 wiring leads into the positive (+) and negative terminals (-) [B in Figure 1] of the tester unit.
B) Connect the clips to the air terminal as shown, making sure that:
1. The electrical contact is good between the clips and terminal (no grease or polluting material).
2. Both clips are connected on 2 distinct parts of the air terminal to test, one on the tip section of the air
terminal, the other on the housing (see photo below).
B) Switch ON the tester unit (“POWER” switch) [E in Figure 1]. The default frequency is 1 kHz, in the opposite case;
press the “Freq” [D in Figure 1] button until frequency is shown as 1 kHz.
C) Set the tester unit in the inductance measurement mode pressing “ZLCR” button [C in Figure 1]. Screen must
show an L. Read and note the L value on the Table 1. This value named X
L
is usually a number with a comma. H
(Henry) is the unit.
D) Set the tester unit in the capacitance measurement mode pressing “ZLCR” button [C in Figure 1]. Screen must
show a C. Read and note the C value on the Table 1. This value named X
C
is usually a number with a comma. ηF
(nano-Farad, 10
-9
Farad) is the unit.
E) Switch OFF the tester unit (“POWER” switch).
(Instructions continued on page 2.)
Warning:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your
ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction, property damage, serious bodily injury
and death.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat,
and gloves as appropriate to the application.