Prior to making a connection, read and follow the full instruction sheet IPRNS, the
full instruction sheet IPP, the full instruction sheet shipped with CADWELD (IPX),
and special instructions below.
Measure outside width of steel beam. Cut copper .25” [6.4 mm] shorter. 1.
Position copper on steel beam .13” [3.2 mm] from ends (As shown above).
Position mold on copper and steel beam (as shown at left). Lock mold securely.2.
Position backing plate on inside of steel beam and copper. The bottom of 3.
backing plate should be even with bottom of mold.
Clamp backing plate and mold together with counter-clamp. Do not over tighten 4.
clamp, as this will force an opening at split of mold.
Check for any openings at bottom of mold and backing plate.5.
®
.13" [3.2 mm] .13" [3.2 mm]
Q.A. Length of CU. Bar
Steel Beam
View Shown
Backing Plates
for Tapered
Beams
Backing Plate
1.5" [38.1 mm]
Copper Lug
Right Hand of Mold
Left Hand of Mold
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
IP6608_B
INSTRUCTION SHEET
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
1 OF 1
© 1995, 2013
ERICO International Corporation
WARNING:
1. ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
damage, serious bodily injury and death.
Bus to vertical Steel
Horizontal Tap on Edge
Vue de la page 0
1

Résumé du contenu

Page 1 - Horizontal Tap on Edge

Prior to making a connection, read and follow the full instruction sheet IPRNS, the full instruction sheet IPP, the full instruction sheet shipped wit

Commentaires sur ces manuels

Pas de commentaire